The B10T is a small brazed plate heat exchanger from SWEP, made of 316/316L stainless steel. It works with both water and refrigerants and is easy to adapt to different uses, such as hot tap water, heating systems, snow melting and heat pumps.
- Up to 140 plates
- For both water and refrigerants
- Brazed, with no gaskets and usually no maintenance
- Small and light, for tight spaces
Sizes and dimensions
The B10T comes with up to 140 plates. Drag the slider to see how the size and weight change with the number of plates.
Connection options
Other connections and special dimensions are available on request.

Threaded connection

Threaded (Ultra High Approved)

Solder connection

Connection plate

Combo connection

Hose connection

O-ring connection

Weld connection
Pressure and temperature
The maximum pressure falls as the temperature rises. Drag the slider to see the design pressure (PED) in each circuit at any temperature.
Temperature
20 °C
Circuit 1
45 bar
Circuit 2
40 bar
Click the chart or drag the slider to pick a temperature.
Material, cleaning and durability
The plates are 316/316L stainless steel brazed together with copper. The largest particle allowed in the fluid is 1 mm, so a filter belongs ahead of the exchanger wherever dirt can get in. It has no gaskets and usually needs no maintenance, but if dirt builds up it can be cleaned in place (CIP). Copper brazing doesn't suit every fluid. If the fluid attacks copper, another material has to be chosen.

Product details
- Maximum flow
9 m³/h
- Material
316/316L stainless steel, copper-brazed
- Design pressure (PED)
About 45 bar in circuit 1 and 40 bar in circuit 2 at room temperature
- Weight without connections
1.15 + 0.096 × NoP kg
- Maximum number of plates (NoP)
140
- Channel volume
0.061 dm³ per side
- Thickness (F)
4.00 + 2.24 × NoP mm
- Dimensions (height × width)
289 × 119 mm
- Maximum particle size
1 mm
- Approvals
PED (Europe), UL (USA), KHK (Japan)
Similar products
We work out the right size with you
Which exchanger fits depends on the job, the temperatures and the flow. Send us the details and we will find the right size, most often from what we have in stock.
Get in touchIt helps if you send us:
- What it is for: heating, tap water, snow melting …
- The power (kW), or the size of the house or area.
- The district heating temperature.
- Temperature and flow on both sides, if you know them.