Skip to content
Verklagnir
SWEP B15T lóðaður plötuvarmaskiptir

SWEP · Heating system

B15T

Brazed plate heat exchanger

Price on request

Choose a size

The B15T is a slim, long brazed plate heat exchanger from SWEP. It is particularly good when the temperature difference between the fluids is very small, the heat flow is high and the energy has to be used well.

  • Made for a very small temperature difference
  • Slim and long, only 76 mm wide
  • Up to 60 plates
  • 316/316L stainless steel, copper-brazed

Sizes and dimensions

The B15T comes with up to 60 plates. Drag the slider to see how the size and weight change with the number of plates.

F1F2F3F4∧B 76D 40A 468C 432FrontG 7F 116E 20Side
The size of the connections (E) depends on the connection type.
50

PriceQuote

Thickness (F)
116mm
Weight without connections
6,45kg
Channels
49
Get in touch

Connection options

Other connections and special dimensions are available on request.

  • Threaded connection

    Threaded connection

  • Threaded (Ultra High Approved)

    Threaded (Ultra High Approved)

  • Solder connection

    Solder connection

Pressure and temperature

The maximum pressure falls as the temperature rises. Drag the slider to see the design pressure (PED) in each circuit at any temperature.

Pressure and temperature35404550-200-1000100200300Temperature (°C)Pressure (bar)

Temperature

20 °C

Circuit 1

48 bar

Circuit 2

48 bar

Click the chart or drag the slider to pick a temperature.

Material, cleaning and durability

The plates are 316/316L stainless steel brazed together with copper. The largest particle allowed in the fluid is 1 mm, so a filter belongs ahead of the exchanger wherever dirt can get in. It has no gaskets and usually needs no maintenance. If dirt builds up it can be cleaned in place (CIP).

Nærmynd af bylgjumynstri í plötupakka

Product details

Maximum flow

4 m³/h

Material

316/316L stainless steel, copper-brazed

Design pressure (PED)

About 48 bar at room temperature, the same in both circuits

Weight without connections

1.25 + 0.104 × NoP kg

Maximum number of plates (NoP)

60

Channel volume

0.063 dm³ per side

Thickness (F)

4.00 + 2.24 × NoP mm

Dimensions (height × width)

468 × 76 mm

Maximum particle size

1 mm

Approvals

PED (Europe), UL (USA), KHK (Japan)

Datasheet (PDF)

We work out the right size with you

Which exchanger fits depends on the job, the temperatures and the flow. Send us the details and we will find the right size, most often from what we have in stock.

Get in touch

It helps if you send us:

  • What it is for: heating, tap water, snow melting …
  • The power (kW), or the size of the house or area.
  • The district heating temperature.
  • Temperature and flow on both sides, if you know them.
  • Which exchanger is in use today, if you are replacing one.